RCBO 6KA 1 POLE + N

KZS-1M RCBO 6KA

  • 2 pole (L+N)
  • Trip characteristics B and C curve
  • Rated residual current 30mA (10mA and 100mA optional)
  • Type A (sinusoidal AC and pulsating DC)
  • IEC rated current In 6 to 25A
  • 18mm wide module
  • Fixing on 35mm DIN rail (IEC/EN 60715)

 They have instantaneous trip characteristics defined as follows:

B-type: Instantaneous trip 3-5 times In

For non-inductive or low inductive loads (heating resistors, generators, very long wire lines)

C-type: Instantaneous trip 5-10 times In

For inductive loads (mixed loads, resistive and inductive with low inrush current)

2 pole B curve 30mA

Order Code Curve

 

IEC

In

IEC

Icn

No. of DIN modules

Weight

 

Type (A)

(kA)

(Kg)

ETI002175201

B

6

6

1

0.115

ETI002175202

B

10

6

1

0.115

ETI002175203

B

13

6

1

0.115

ETI002175204

B

16

6

1

0.115

ETI002175205

B

20

6

1

0.115

ETI002175206

B

25

6

1

0.115

2 pole C curve 30mA  

 

 

 

ETI002175221

C

6

6

1

0.115

ETI002175222

C

10

6

1

0.115

ETI002175223

C

13

6

1

0.115

ETI002175224

C

16

6

1

0.115

ETI002175225

C

20

6

1

0.115

ETI002175226

C

25

6

1

0.115

 Compliance and standards

Certifications obtained: CE, VDE, KEMA, SAA Certificate No. SAA-150148-EA

Compliant with standards: IEC 61009, AS/NZS 61009.1:2011