RTOX Output Line Reactors

Polylux RTOX Output Line Reactors

 

Polylux RTOX Output Line Reactors for AC Drives

 

  • Operational Characteristics:

– Three phase output reactors for AC drives.
– Attenuate voltage spikes on drive output.
– Reduction of reflection effect on long cable lengths between drive and motor.
– Recommended for cable length of 50m+.
– Rated currents from 2.5-630A.
– Thermal over temperature protection.
– Custom designs available.
– Rated Voltage: Line voltage 380-460V 50/60Hz.
– Isolation: Class F – 155°C.
– Winding: Class HC- 200°C.
– Thermal Overload Factor: 5%.
– Voltage Drop: 3% at 400V 50Hz and nominal current.
– Test Voltage: 3kV (1 min, 50Hz).
– Protection: IP00.
– Temp Rating: +40°C.
– Temperature Rise: <90°C.
– Connection: Terminals or lugs.
– Construction: Aluminium windings.
– Standards: IEC/EN/UNE-EN 60076-6, CE.

 

Order Code Rated Current (A) @40°C  L (mH) Dimensions
A x B x C (mm) 
 Weight (kg)
18RTOX025 2.5 8.821 150 x 110 x 184 2.0
18RTOX040 4 5.513 150 x 120 x 185 3.2
18RTOX050 5 4.411 150 x 120 x 185 3.3
18RTOX063 6.3 3.501 150 x 120 x 185 3.4
18RTOX080 8 2.757 150 x 125 x 185 4.0
18RTOX100 10 2.205 150 x 130 x 185 4.7
18RTOX160 16 1.378 150 x 140 x 185 6.3
18RTOX200 20 1.103 150 x 150 x 185 7.8
18RTOX250 25 0.882 150 x 155 x 185 8.5
18RTOX315 31.5 0.700 180 x 150 x 220 11.1
18RTOX400 40 0.551 180 x 165 x 220 13.9
18RTOX500 50 0.441 180 x 180 x 220 16.7
18RTOX630 63 0.350 180 x 205 x 220 21.3
18RTOX800 80 0.276 240 x 175 x 294 27.3
18RTOX1000 100 0.221 240 x 190 x 294 32.4
18RTOX1250 125 0.176 240 x 215 x 294 40.7
18RTOX1600 160 0.138 340 x 219 x 375 38.7
18RTOX2000 200 0.110 340 x 239 x 375 49.1
18RTOX2500 250 0.088 340 x 259 x 375 59
18RTOX3150 315 0.070 340 x 294 x 375 77
18RTOX4000 400 0.055 340 x 319 x 375 93
18RTOX5000 500 0.044 410 x 319 x 445 128
18RTOX6300 630 0.035 410 x 359 x 445 159